Article Groups
Service
|
|
Copper and aluminium stranded conductors
acc. to DIN 48201 part 1 and 5
Technical data
Construction and application
Stranded conductors consisting out of copper or aluminium wires with
stronger wire-Ø and an corresponding breaking load of the ropes.
Applications as electrical conductors inside of energy supply companies.
The values of the current capacity are in accordance with DIN 48201.
They are approximate values by a frequency up to 60 hertz and a wind
velocity of 0,6 m per second and solar influence for an initial
atmospheric temperature of +35° C and a maximum cable temperature of
+80° C. In special cases where there is a complete lack of wind the
figures should be reduced by average of about 30 %. |
Technical data
Material copper
- Cu-ETP1 wires acc. to DIN EN 13602
- wire-Ø from 1,35 mm up to 3,25 mm
Surface
Delivery
- in rings or on wooden drums
|
Technical data
Material aluminium
- hard aluminium wires
- wire-Ø from 1,7 mm up to 3,74 mm
Surface
Delivery
- in rings or on wooden drums
|
|
Part-No. material copper |
technical data |
uncoated
hard |
uncoated
soft |
tinned |
cross-section
mm2 |
current-
load |
dimensions mm |
weight
kg/% m |
diameter and number of wires |
outside-Ø |
|
60001 |
60051 |
60052 |
10 |
90 A |
7 |
x |
1,35 |
4,1 |
9,00 |
|
60003 |
60053 |
60054 |
16 |
125 A |
7 |
x |
1,70 |
5,1 |
14,30 |
|
60005 |
60055 |
60056 |
25 |
160 A |
7 |
x |
2,10 |
6,3 |
21,80 |
|
60007 |
60057 |
60058 |
35 |
200 A |
7 |
x |
2,50 |
7,5 |
31,00 |
|
60009 |
60059 |
60060 |
50 |
250 A |
7 |
x |
3,00 |
9,0 |
44,60 |
|
60011 |
60061 |
60062 |
50 |
250 A |
19 |
x |
1,80 |
9,0 |
43,70 |
|
60013 |
60063 |
60064 |
70 |
310 A |
19 |
x |
2,10 |
10,5 |
59,60 |
|
60015 |
60065 |
60066 |
95 |
380 A |
19 |
x |
2,50 |
12,5 |
84,50 |
|
60017 |
60067 |
60068 |
120 |
440 A |
19 |
x |
2,80 |
14,0 |
106,00 |
|
60019 |
60069 |
60070 |
150 |
510 A |
37 |
x |
2,25 |
15,8 |
133,70 |
|
60021 |
60071 |
60072 |
185 |
585 A |
37 |
x |
2,50 |
17,5 |
164,90 |
|
60023 |
60073 |
60074 |
240 |
700 A |
61 |
x |
2,25 |
20,3 |
220,90 |
|
60025 |
60075 |
60076 |
300 |
800 A |
61 |
x |
2,50 |
22,5 |
272,50 |
|
60027 |
60077 |
60078 |
400 |
950 A |
61 |
x |
2,89 |
26,0 |
364,00 |
|
60029 |
60079 |
60080 |
500 |
1110 A |
61 |
x |
3,23 |
29,1 |
454,50 |
|
|
|
|
|
Part-No.
AL uncoated |
technical data |
|
cross-section mm2 |
current-load |
dimensions mm |
weight kg/% m |
|
diameter and number of wires |
outside-Ø |
|
60002 |
16 |
110 A |
7 |
x |
1,70 |
5,1 |
4,30 |
|
60004 |
25 |
145 A |
7 |
x |
2,10 |
6,3 |
6,60 |
|
60006 |
35 |
180 A |
7 |
x |
2,50 |
7,5 |
9,40 |
|
60008 |
50 |
225 A |
7 |
x |
3,00 |
9,0 |
13,50 |
|
60010 |
50 |
225 A |
19 |
x |
1,80 |
9,0 |
13,50 |
|
60012 |
70 |
270 A |
19 |
x |
2,10 |
10,5 |
18,10 |
|
60014 |
95 |
340 A |
19 |
x |
2,50 |
12,5 |
25,60 |
|
60016 |
120 |
390 A |
19 |
x |
2,80 |
14,0 |
32,20 |
|
60018 |
150 |
455 A |
37 |
x |
2,25 |
15,8 |
40,60 |
|
60020 |
185 |
520 A |
37 |
x |
2,50 |
17,5 |
50,00 |
|
60022 |
240 |
625 A |
61 |
x |
2,25 |
20,3 |
67,00 |
|
60024 |
300 |
710 A |
61 |
x |
2,50 |
22,5 |
82,70 |
|
60026 |
400 |
855 A |
61 |
x |
2,89 |
26,0 |
110,40 |
|
60028 |
500 |
990 A |
61 |
x |
3,23 |
29,1 |
137,90 |
|
60030 |
625 |
1140 A |
91 |
x |
2,96 |
32,6 |
173,20 |
|
60032 |
800 |
1340 A |
91 |
x |
3,35 |
36,9 |
221,80 |
|
60034 |
1000 |
1540 A |
91 |
x |
3,74 |
41,1 |
276,70 |
|
|