Copper and aluminium stranded conductors
acc. to DIN 48201 part 1 and 5

Technical data

Construction and application

Stranded conductors consisting out of copper or aluminium wires with stronger wire-Ø and an corresponding breaking load of the ropes. Applications as electrical conductors inside of energy supply companies. The values of the current capacity are in accordance with DIN 48201. They are approximate values by a frequency up to 60 hertz and a wind velocity of 0,6 m per second and solar influence for an initial atmospheric temperature of +35° C and a maximum cable temperature of +80° C. In special cases where there is a complete lack of wind the figures should be reduced by average of about 30 %.

Technical data
Material copper
  • Cu-ETP1 wires acc. to DIN EN 13602
  • wire-Ø from 1,35 mm up to 3,25 mm
Surface
  • uncoated or tinned
Delivery
  • in rings or on wooden drums
Technical data
Material aluminium
  • hard aluminium wires
  • wire-Ø from 1,7 mm up to 3,74 mm
Surface
  • uncoated
Delivery
  • in rings or on wooden drums
 

 

uncoated
soft
tinned
outside-Ø
   60001   60051   60052   10   90 A   7   x   1,35   4,1   9,00 
   60003   60053   60054   16   125 A   7   x   1,70   5,1   14,30 
   60005   60055   60056   25   160 A   7   x   2,10   6,3   21,80 
   60007   60057   60058   35   200 A   7   x   2,50   7,5   31,00 
   x   3,00   9,0 
   60011   60061   60062   50   250 A   19   x   1,80   9,0   43,70 
   60013   60063   60064   70   310 A   19   x   2,10   10,5   59,60 
   60015   60065   60066   95   380 A   19   x   2,50   12,5   84,50 
   x   2,80   14,0 
   60019   60069   60070   150   510 A   37   x   2,25   15,8   133,70 
   x   2,50   17,5 
   60023   60073   60074   240   700 A   61   x   2,25   20,3   220,90 
   60025   60075   60076   300   800 A   61   x   2,50   22,5   272,50 
   60027   60077   60078   400   950 A   61   x   2,89   26,0   364,00 
   60029   60079   60080   500   1110 A   61   x   3,23   29,1   454,50 
   
 
   current-load 
  outside-Ø 
   60002   16   110 A   7   x   1,70   5,1   4,30 
   60004   25   145 A   7   x   2,10   6,3   6,60 
   60006   35   180 A   7   x   2,50   7,5   9,40 
   x   3,00   9,0 
   60010   50   225 A   19   x   1,80   9,0   13,50 
   60012   70   270 A   19   x   2,10   10,5   18,10 
   60014   95   340 A   19   x   2,50   12,5   25,60 
   x   2,80   14,0 
   60018   150   455 A   37   x   2,25   15,8   40,60 
   x   2,50   17,5 
   60022   240   625 A   61   x   2,25   20,3   67,00 
   60024   300   710 A   61   x   2,50   22,5   82,70 
   60026   400   855 A   61   x   2,89   26,0   110,40 
   x   3,23   29,1 
   60030   625   1140 A   91   x   2,96   32,6   173,20 
   60032   800   1340 A   91   x   3,35   36,9   221,80 
   60034   1000   1540 A   91   x   3,74   41,1   276,70 
to the top