Article Groups
Service
|
design A
design B
Part-No. 15577
|
Flexible insulated earthing tapes and copper connectors 10-210 mm2
with solderless pressed contact areas
Technical data Construction and
application Manufactured by flexible PVC-extruded braided copper
tapes with solderless pressed contact areas made out of seamless
Cu-ETP-tubes. The crimping process is realized without using additives
like tin or soldering and welding additives. We use exclusively
materials of same analysis and same conductivity of 57 S (braids and
tubes). So the hereby used druseidtpress technology guarantee a
extreme compressing and a optimal contact resistance by compressing the
wires so much, that no harmful gases or other environmental influences
can go inside. By using our connectors you can be sure to have a very
well and optimized contact resistance.
Caused by the technical characteristics of the insulating material
and the flexibility of the braids the connectors offer multifarious
applications inside switchgears or control panel devices up to app. 730
A as well as earthing connections. Technical data
Electrical conductor
- braided copper tapes made out of Cu-ETP-wires
- annealed, uncoated wires
wire-Ø 0,15 mm (10/16 mm2)
wire-Ø 0,20 mm (25-210 mm2)
Contact areas
- seamless copper tubes made out of Cu-ETP material
- surface uncoated or tinned
Insulation
- special vinyl compound
- black, free of lead
- self-extinguishing acc. to UL 94 VO
- elasticity 365%
- dielectric strength 20 kV/mm
- operating voltage max. 1 kV
- operating temperature -20° C up to +105° C
|
|
Part-No. |
technical data |
design A |
design B |
cross-section
mm² |
current-
load |
dimensions mm |
B1 |
B2 |
ca. s |
d |
L |
|
15415 |
15560 |
10 |
75-105 A |
12 |
12 |
3,0 |
5,5 |
|
|
15416 |
15561 |
16 |
100-150 A |
15 |
15 |
3,3 |
6,5 |
|
|
15417 |
15562 |
25 |
145-210 A |
20 |
20 |
3,8 |
9 |
|
|
15418 |
15563 |
25 |
145-210 A |
25 |
25 |
3,5 |
9 |
|
|
15419 |
15564 |
35 |
170-250 A |
20 |
20 |
4,3 |
9 |
|
|
15420 |
15565 |
35 |
170-250 A |
25 |
25 |
3,6 |
9 |
|
|
15421 |
15566 |
50 |
205-300 A |
25 |
25 |
4,7 |
9 |
|
|
15422 |
15567 |
50 |
215-310 A |
30 |
30 |
4,3 |
11 |
|
|
15423 |
15568 |
70 |
245-355 A |
25 |
25 |
6,0 |
9 |
|
|
15424 |
15569 |
70 |
245-355 A |
30 |
30 |
5,0 |
11 |
|
|
15425 |
15570 |
70 |
270-390 A |
35 |
35 |
5,4 |
11 |
|
|
15426 |
15571 |
70 |
270-390 A |
40 |
40 |
5,2 |
14 |
|
|
15427 |
15572 |
100 |
325-470 A |
35 |
35 |
6,1 |
11 |
|
|
15428 |
15573 |
100 |
325-470 A |
40 |
40 |
7,2 |
14 |
|
|
15429 |
15574 |
120 |
375-540 A |
40 |
40 |
8,0 |
14 |
|
|
- |
15575 |
140 |
405-580 A |
40 |
40 |
8,6 |
14 |
|
|
- |
15576 |
210 |
505-730 A |
40 |
40 |
9,8 |
14 |
|
|
- |
15577 |
210 |
505-730 A |
50 |
50 |
8,0 |
14 |
|
|
Remark: Manufacturing acc. to the customers’ wishes in large as well as
small quantities. Uncoated braid and uncoated contact areas are standard.
But on request with tinned contact areas and bare braid or with changed
drill holes deliverable. By ordering the design with tinned contact areas it
is necessary to add the word tinned behind the part-No. (e.g. 15570 tinned).
All information about current load are approximate values in consideration
of the cables heat for single laying of air cooled cables and ambient
temperature +35° C. Minimum value = conductor temperature app. +65° C.
Maximum value conductor temperature app. +90° C. The temperature of the
conductor is in dependent on the installation, the application, the cooling,
the ambient temperature etc., so that if necessary reducing factors are to
be considered. With pleasure our employees assist your company in finding
optimal solutions. |
Enquiry form
|