Article Groups
Service
|
|
Insulated earthing ropes ESY
flexible, without overall copper braid
Technical data
Construction and application
Comparable applications like the ESUY material but manufactured out
of wires with a stronger wire-Ø of 0,2 mm and without a additional
overall copper braid. Further applications and demands are contained in
the regulations of the EN 61230 respectively VDE 0683 part 100.
Technical data
Conductor
- round stranded copper cables made out of annealed CU-ETP1 wires
acc. to DIN EN 13602
- wire-Ø 0,2 mm
- surface uncoated
Insulation material
- PVC
- colour transparent
- operating temperature
fixed -20° C up to +70° C
moved -5° C up to +70° C
Delivery
|
|
Part-No.
|
technical data |
cross-section
mm2 |
current-
load |
dimensions mm |
weight
kg/% m |
diameter and number of wires |
outside-Ø |
|
02920 |
16 |
4,5 kA |
525 |
x |
0,20 |
8,4 |
18,20 |
|
02921 |
25 |
7,0 kA |
800 |
x |
0,20 |
9,8 |
26,50 |
|
02922 |
35 |
10,0 kA |
1120 |
x |
0,20 |
11,4 |
36,50 |
|
02923 |
50 |
14,0 kA |
1615 |
x |
0,20 |
13,8 |
53,70 |
|
02924 |
70 |
19,5 kA |
2250 |
x |
0,20 |
15,8 |
74,70 |
|
02925 |
95 |
26,5 kA |
3085 |
x |
0,20 |
18,2 |
99,60 |
|
02926 |
120 |
33,5 kA |
3820 |
x |
0,20 |
20,1 |
122,00 |
|
02927 |
150 |
42,0 kA |
4800 |
x |
0,20 |
22,0 |
152,00 |
|
Remark: The fixed values about current load are by an ambient
temperature +20° C and a conductor heat of +250° C. This temperature is
allowed for a period of max. 0,5 sec. inside of AC- and three current phase
equipments. |
|