Tightening force for leadings and cables



 

The tightening force is the identified value to pull out a leading or cable out of the crimped connector. The values deliver information about the mechanical stress of crimping connections. In dependence of the different cable lugs and connectors we have different regulations about the minimum tightening forces for crimping connections. To pass the test acc. to the different norms and regulations it is necessary that the electrical conductor cannot pulled out inside of 60 seconds
when testing with 100 % of the tightening force.
Following a summary of such values under consideration of the different norms.

 


Values for crimping copper connectors up to 10 mm²
DIN EN 61238-1,
3/2004 (VDE 0220 part 100) exept cable end sleeves
Values for crimping aluminium connectors up to 16 mm²
DIN EN 61238-1,
03/2004 (VDE 0220 part 100)
  100% 130% 150% 100% 130% 150%
10   mm² 600     N 780     N 90      N - - -
16   mm² 960     N 1248   N 1440   N 640     N 832     N 960     N
25   mm² 1500   N 1950   N 2250   N 1000   N 1300   N 1500   N
35   mm² 2100   N 2730   N 3150   N 1400   N 1820   N 2100   N
50   mm² 3000   N
3900   N 4500   N 2000   N 2600   N 3000   N
70   mm² 4200   N 5460   N 6300   N 2800   N 3640   N 4200   N
95   mm² 5700   N 7410   N 8550   N 3800   N 4940   N 5700   N
120 mm² 7200   N 9360   N 10800 N 4800   N 6240   N 7200   N
150 mm² 9000   N 11700 N 13500 N 6000   N 7800   N 9000   N
185 mm² 11100 N 14430 N 16550 N 7400   N 9620   N 11100 N
240 mm² 14400 N 18720 N 21600 N 9600   N 12480 N 14400 N
300 mm² 18000 N 23400 N 27000 N 12000 N 15600 N 18000 N
400 mm² 24000 N*     16000 N 20800 N 24000 N
500 mm² 30000 N*     20000 N 26000 N 30000 N
625 mm² 37500 N*     25000 N*    
800 mm² 48000 N*     32000 N*    
1000mm² 60000 N*     40000 N*    
* VDE 0220 part 100: maximum value is limited up to 20000 N

 

 

 


Values for crimp connections up to 10 mm²
EN 60352 part 2, 10/2002 exept cable end sleeves
  Values for connections with tabs and receptacles in combination
with copper conductors DIN EN 61210 (VDE 0613 part 6), 06/2011
cross-section 100% 130% 150%   100%
0,2 mm² - - -   28   N
0,34 mm² - - -   40   N
0,5 mm² 60   N 78   N 90   N   56   N
0,75 mm² 85   N 111 N 128 N   84   N
1 mm² 108 N 140 N 162 N   108 N
1,5 mm² 150 N 195 N 225 N   150 N
2,5 mm² 230 N 299 N 345 N   230 N
4 mm² 310 N 403 N 465 N   310 N
6 mm² 360 N 468 N 540 N   360 N
10 mm² 380 N 494 N 570 N   -

 

Values for cable end sleeves
Values for cable end sleeves
cross-section EN 60947-1
(VDE 0660 part 100)
release 04/2008
EN 60999-1
release 12/2000
cross-section EN 60947-1
(VDE 0660 Teil 100)
Stand 04/2008
EN 60999-2
release 4/2004
0,2   mm² 10 N 10 N 50   mm² 236 N 236 N
0,34 mm² 15 N 15 N 70   mm² 285 N 285 N
0,5   mm² 20 N 20 N 95   mm² 351 N 351 N
0,75 mm² 30 N 30 N 120 mm² 427 N 427 N
1      mm² 35 N 35 N 150 mm² 427 N 427 N
1,5   mm² 40 N 40 N 185 mm² 503 N 503 N
2,5   mm² 50 N 50 N 240 mm² 578 N 578 N
4      mm² 60 N 60 N      
6      mm² 80 N 80 N      
10    mm² 90 N 90 N      
16    mm² 100 N 100 N      
25    mm² 135 N 135 N      
35    mm² 190 N 190 N      

 

 

 

 
 