Article Groups
Service
|
|
Tightening force for leadings and cables |
|
|
|
|
The tightening force is the identified value to pull out a leading or cable
out of the crimped connector. The values deliver information about the
mechanical stress of crimping connections. In dependence of the different
cable lugs and connectors we have different regulations about the
minimum tightening forces for crimping connections.
To pass the test acc. to the different norms and regulations it is necessary
that the electrical conductor cannot pulled out inside of 60 seconds
when testing with 100 % of the tightening force.
Following a summary
of such values under consideration of the different norms.
|
Values for crimping copper connectors up to 10 mm²
DIN EN 61238-1,
3/2004 (VDE 0220 part 100) exept cable end sleeves |
Values for crimping aluminium connectors up to 16 mm²
DIN EN 61238-1,
03/2004 (VDE 0220 part 100) |
|
100% |
130% |
150% |
100% |
130% |
150% |
10 mm² |
600 N |
780 N |
90 N |
- |
- |
- |
16 mm² |
960 N |
1248 N |
1440 N |
640 N |
832 N |
960 N |
25 mm² |
1500 N |
1950 N |
2250 N |
1000 N |
1300 N |
1500 N |
35 mm² |
2100 N |
2730 N |
3150 N |
1400 N |
1820 N |
2100 N |
50 mm² |
3000 N
|
3900 N |
4500 N |
2000 N |
2600 N |
3000 N |
70 mm² |
4200 N |
5460 N |
6300 N |
2800 N |
3640 N |
4200 N |
95 mm² |
5700 N |
7410 N |
8550 N |
3800 N |
4940 N |
5700 N |
120 mm² |
7200 N |
9360 N |
10800 N |
4800 N |
6240 N |
7200 N |
150 mm² |
9000 N |
11700 N |
13500 N |
6000 N |
7800 N |
9000 N |
185 mm² |
11100 N |
14430 N |
16550 N |
7400 N |
9620 N |
11100 N |
240 mm² |
14400 N |
18720 N |
21600 N |
9600 N |
12480 N |
14400 N |
300 mm² |
18000 N |
23400 N |
27000 N |
12000 N |
15600 N |
18000 N |
400 mm² |
24000 N* |
|
|
16000 N |
20800 N |
24000 N |
500 mm² |
30000 N* |
|
|
20000 N |
26000 N |
30000 N |
625 mm² |
37500 N* |
|
|
25000 N* |
|
|
800 mm² |
48000 N* |
|
|
32000 N* |
|
|
1000mm² |
60000 N* |
|
|
40000 N* |
|
|
* VDE 0220 part 100: maximum value is limited up to 20000 N |
|
|
Values for crimp connections up to 10 mm²
EN 60352 part 2, 10/2002 exept cable end sleeves |
|
Values for connections with tabs and receptacles in combination
with copper conductors DIN EN 61210 (VDE 0613 part 6), 06/2011 |
cross-section |
100% |
130% |
150% |
|
100% |
0,2 mm² |
- |
- |
- |
|
28 N |
0,34 mm² |
- |
- |
- |
|
40 N |
0,5 mm² |
60 N |
78 N |
90 N |
|
56 N |
0,75 mm² |
85 N |
111 N |
128 N |
|
84 N |
1 mm² |
108 N |
140 N |
162 N |
|
108 N |
1,5 mm² |
150 N |
195 N |
225 N |
|
150 N |
2,5 mm² |
230 N |
299 N |
345 N |
|
230 N |
4 mm² |
310 N |
403 N |
465 N |
|
310 N |
6 mm² |
360 N |
468 N |
540 N |
|
360 N |
10 mm² |
380 N |
494 N |
570 N |
|
- |
Values for cable end sleeves
|
Values for cable end sleeves |
|
cross-section |
EN 60947-1
(VDE 0660 part 100)
release 04/2008 |
EN 60999-1
release 12/2000 |
cross-section |
EN 60947-1
(VDE 0660 Teil 100)
Stand 04/2008 |
EN 60999-2
release 4/2004 |
0,2 mm² |
10 N |
10 N |
50 mm² |
236 N |
236 N |
0,34 mm² |
15 N |
15 N |
70 mm² |
285 N |
285 N |
0,5 mm² |
20 N |
20 N |
95 mm² |
351 N |
351 N |
0,75 mm² |
30 N |
30 N |
120 mm² |
427 N |
427 N |
1 mm² |
35 N |
35 N |
150 mm² |
427 N |
427 N |
1,5 mm² |
40 N |
40 N |
185 mm² |
503 N |
503 N |
2,5 mm² |
50 N |
50 N |
240 mm² |
578 N |
578 N |
4 mm² |
60 N |
60 N |
|
|
|
6 mm² |
80 N |
80 N |
|
|
|
10 mm² |
90 N |
90 N |
|
|
|
16 mm² |
100 N |
100 N |
|
|
|
25 mm² |
135 N |
135 N |
|
|
|
35 mm² |
190 N |
190 N |
|
|
|
|
|
|
|
|