Article Groups
Service
|
Table for the current load of copper busbars acc. to DIN
43671
|
|
continous currents in A |
width x
thickness mm |
material |
AC up to 60 Hz |
DC/AC up to 16 2/3 Hz |
coated |
uncoated |
coated |
uncoated |
number of
busbars |
number of
busbars |
number of
busbars |
number of
busbars |
1 |
2 |
3 |
4 |
1 |
2 |
3 |
4 |
1 |
2 |
3 |
4 |
1 |
2 |
3 |
4 |
I |
II |
III |
II50II |
I |
II |
III |
II50II |
I |
II |
III |
IIII |
I |
II |
III |
IIII |
12 |
x |
2 |
|
123 |
202 |
228 |
|
108 |
182 |
216 |
|
123 |
202 |
233 |
|
108 |
182 |
220 |
|
15 |
x |
2 |
|
148 |
240 |
261 |
|
128 |
212 |
247 |
|
148 |
240 |
267 |
|
128 |
212 |
252 |
|
15 |
x |
3 |
|
187 |
316 |
381 |
|
162 |
282 |
361 |
|
187 |
316 |
387 |
|
162 |
282 |
365 |
|
20 |
x |
2 |
|
189 |
302 |
313 |
|
162 |
264 |
298 |
|
189 |
302 |
321 |
|
162 |
266 |
303 |
|
20 |
x |
3 |
|
237 |
394 |
454 |
|
204 |
348 |
431 |
|
237 |
394 |
463 |
|
204 |
348 |
437 |
|
20 |
x |
5 |
|
319 |
560 |
728 |
|
274 |
500 |
690 |
|
320 |
562 |
729 |
|
274 |
502 |
687 |
|
20 |
x |
10 |
|
497 |
924 |
1320 |
|
427 |
825 |
1180 |
|
499 |
932 |
1300 |
|
428 |
832 |
1210 |
|
25 |
x |
3 |
|
287 |
470 |
525 |
|
245 |
412 |
498 |
|
287 |
470 |
536 |
|
245 |
414 |
506 |
|
25 |
x |
5 |
|
384 |
662 |
869 |
|
327 |
586 |
795 |
|
384 |
664 |
841 |
|
327 |
590 |
794 |
|
30 |
x |
3 |
|
337 |
544 |
593 |
|
285 |
476 |
564 |
|
337 |
546 |
608 |
|
286 |
478 |
575 |
|
30 |
x |
5 |
|
447 |
760 |
944 |
|
379 |
672 |
896 |
|
448 |
766 |
950 |
|
380 |
676 |
897 |
|
30 |
x |
10 |
E-Cu F30/ |
676 |
1200 |
1670 |
|
573 |
1060 |
1480 |
|
683 |
1230 |
1630 |
|
579 |
1080 |
1520 |
|
40 |
x |
3 |
Cu-ETP |
435 |
692 |
725 |
|
366 |
600 |
690 |
|
436 |
696 |
748 |
|
367 |
604 |
708 |
|
40 |
x |
5 |
4/4 hard |
573 |
952 |
1140 |
|
482 |
836 |
1090 |
|
576 |
966 |
1160 |
|
484 |
848 |
1100 |
|
40 |
x |
10 |
|
850 |
1470 |
2000 |
2580 |
715 |
1290 |
1770 |
2280 |
865 |
1530 |
2000 |
|
728 |
1350 |
1880 |
|
50 |
x |
5 |
|
697 |
1140 |
1330 |
2010 |
583 |
994 |
1260 |
1920 |
703 |
1170 |
1370 |
|
588 |
1020 |
1300 |
|
50 |
x |
10 |
|
1020 |
1720 |
2320 |
2950 |
852 |
1510 |
2040 |
2600 |
1050 |
1830 |
2360 |
|
875 |
1610 |
2220 |
|
60 |
x |
5 |
|
826 |
1330 |
1510 |
2310 |
688 |
1150 |
1440 |
2210 |
836 |
1370 |
1580 |
2060 |
696 |
1190 |
1500 |
1970 |
60 |
x |
10 |
|
1180 |
1960 |
2610 |
3290 |
985 |
1720 |
2300 |
2900 |
1230 |
2130 |
2720 |
3580 |
1020 |
1870 |
2570 |
3390 |
80 |
x |
5 |
|
1070 |
1680 |
1830 |
2830 |
885 |
1450 |
1750 |
2720 |
1090 |
1770 |
1990 |
2570 |
902 |
1530 |
1890 |
2460 |
80 |
x |
10 |
|
1500 |
2410 |
3170 |
3930 |
1240 |
2110 |
2790 |
3450 |
1590 |
2730 |
3420 |
4490 |
1310 |
2380 |
3240 |
4280 |
100 |
x |
5 |
|
1300 |
2010 |
2150 |
3300 |
1080 |
1730 |
2050 |
3190 |
1340 |
2160 |
2380 |
3080 |
1110 |
1810 |
2270 |
2960 |
100 |
x |
10 |
|
1810 |
2850 |
3720 |
4530 |
1490 |
2480 |
3260 |
3980 |
1940 |
3310 |
4100 |
5310 |
1600 |
2890 |
3900 |
5150 |
120 |
x |
10 |
|
2110 |
3280 |
4270 |
5130 |
1740 |
2860 |
3740 |
4500 |
2300 |
3900 |
4780 |
6260 |
1890 |
3390 |
4560 |
6010 |
160 |
x |
10 |
|
2700 |
4130 |
5360 |
6320 |
2220 |
3590 |
4680 |
5530 |
3010 |
5060 |
6130 |
8010 |
2470 |
4400 |
5860 |
7110 |
200 |
x |
10 |
|
3290 |
4970 |
6430 |
7490 |
2690 |
4310 |
5610 |
6540 |
3720 |
6220 |
7460 |
9730 |
3040 |
5390 |
7150 |
9390 |
|
Remark: Continuous currents for busbars Cu-ETP/E-Cu according to the
DIN regulations for rectangular bars in interieur systems at +35° C air
temperature and + 65° C bar temperature and vertical bar position, bar
packages with spaces like the bar thickness respectively minimum 50 mm by
laying of 4 busbars or when working with AC-current with a main distance of
> 0,8 x main conductor distance (measured middle to middle of the bars).
Values for a changed ambient temperature and reducing factors for changed
applications are contained in the DIN 43671. |
|